| MAIN FEATURES | |
|---|---|
| Capacity | 10kVA/8KW |
| Model | HT1110KS/KL |
| Brand | G-Mac |
| Brand Origin | Germany |
| Technology | Online Transformer Based Industrial UPS |
| INPUT | |
| Phase | Single Phase to ground (P+N+E) |
| Voltage Range |
110-300VAC±60%(Load) 160-300VAC±100% (Load) |
| Frequency Range | 50Hz/60(Default) ± 5% Can be adjust |
| Power Factor | ≥0.99 @ Nominal Voltage |
| OUTPUT | |
| Output Voltage | 220VAC+1%(208,210,230,240 Adjustable) |
| Voltage Ragulation | ±1% |
| Frequency Range |
Synchronize Correction Range-47-53Hz or 57-63Hz Battery mode-50Hz/60Hz(Adjustable)+0.25Hz |
| Surge Ratio | 3:1 |
| Todal Hammonic distortion | ≤3%THD(Linear load) ≤5%THD(Non-linear load) |
| Transfer time |
ACto DC-0ms Invertion to bypass-4ms(Standard) |
| Waveform | pure sine wave |
| BATTERY | |
| Battery model | Depends on customer requirments |
| Quantity | 3 PCS |
| Maximun Charging | (1-12)AMP- adjustable |
| Charging Voltage | 41.0VDC±1% |
| WARNING | |
| Battery Model | Alarms beeps every 4 seconds |
| Low Battery | Alarms beeps every seconds |
| Overload | Alarms beeps every seconds |
| Fault | Alarms beeps every seconds |
| SYSTEM FEATURES | |
| Temperature & Humidity |
Relative humidity-20-90% temperature- 0-40°C |
| Noise | <50dBA@ 1 meter |
| LED/LCD display | System state, Load power, battery capacity, utility power mode, battery mode, bypass mode, fault indicator |
| Communication interface | Support windows@2000/2003/XP/Vista/2008 |
| Dimension | 460mm×190mm×615mm/ 395mm×190mm×325mm |
| Weight (Kg) | 54.20 / 47.80 (Approx) |
Application
1. What is the HAMBURG-HT1110KS?
The HAMBURG-HT1110KS is a 10kVA True Online Double-Conversion UPS designed to provide uninterrupted and stable power for servers, data centers, networking equipment, and sensitive electronics.
2. What is the power capacity of the UPS?
The UPS provides 10kVA / 8000W power capacity.
3. What UPS technology does it use?
It uses True Online Double-Conversion technology with DSP control for maximum power protection.
4. What is the input voltage range?
The UPS supports a wide input voltage range from 110V to 300V AC depending on load condition.
5. What is the output voltage?
The output voltage can be configured to 220V, 230V, or 240V AC.
6. Does it provide pure sine wave output?
Yes, it provides pure sine wave output suitable for sensitive electronic devices.
7. What is the input frequency range?
The UPS supports an input frequency range of 40Hz to 70Hz.
8. What is the output frequency?
The output frequency is 50/60Hz with high precision regulation in battery mode.
9. What is the battery configuration?
The UPS uses a 192V DC battery system with sixteen 12V batteries connected in series.
10. What type of batteries are used?
It uses sealed maintenance-free lead-acid (SMF) batteries.
11. How long is the backup time?
Typical backup time is approximately 3.5 minutes at 80% load, depending on battery condition and connected load.
12. How long does the battery take to charge?
The batteries usually recharge to around 90% capacity within 8 hours.
13. What is the charging current?
The standard charging current is approximately 1A.
14. What is the output power factor?
The output power factor is 0.9 depending on the model version.
15. What is the efficiency of the UPS?
Efficiency can reach:
16. Does it support ECO mode?
Yes, the UPS includes ECO mode for energy-saving operation.
17. Does it have an LCD display?
Yes, the UPS includes an LED + LCD display for monitoring:
18. What communication ports are available?
The UPS supports:
19. Does it support remote monitoring?
Yes, remote monitoring is available through the optional SNMP card.
20. Is the UPS generator compatible?
Yes, the UPS is compatible with generators.
21. Does it have surge protection?
Yes, it includes surge and lightning protection features.
22. What overload protection features are included?
The UPS includes overload, short-circuit, over-temperature, and battery protection systems.
23. What is the transfer time?
Transfer time between mains and battery mode is 0ms in online mode.
24. What is the operating temperature range?
Recommended operating temperature is 0°C to 40°C.
25. What humidity level is supported?
The UPS supports up to 95% non-condensing humidity.
26. How noisy is the UPS?
Noise level is generally below 48–50dB at normal load conditions.
27. What applications is this UPS suitable for?
It is suitable for:
28. What is the approximate weight of the UPS?
The UPS weighs approximately 60–75 kg depending on battery configuration.
29. What is the warranty period?
The standard warranty period is generally 1–2 years depending on supplier policy.
30. Can it operate continuously?
Yes, the UPS is designed for continuous 24/7 online operation for critical equipment protection.