| MAIN FEATURES | |
|---|---|
| Capacity | 3KVA/2.4kW |
| Model | DRESDEN-LF1103KS |
| Brand | G-Mac |
| Brand Origin | Germany |
| Technology | IGBT inverter and output isolation transformer |
| INPUT | |
| Phase | Single Phase 3 wires |
| Rated Voltage | 220±5% |
| Frequency Range | 40-66(Automatically Select Synchronization range according to grid frequency) |
| Range Power Factor | >0.97(with filter) |
| Battery Voltage | 96VDC |
| OUTPUT | |
| Output Voltage | 220/230/240Vac |
| Voltage regulation | ±1% |
| Frequency | 50/60±0.05%(battery mode) |
| Waveform | Sine Wave, THD<3% |
| Efficiency | Online:90% |
| Power factor | 0.8/0.9(Option) |
| Overload | 110%-129% full load keep10min; 130%-150%load keep for 60s |
| OTHERS | |
| Crest Factor | >3:1 |
| Display | LED display work status and fault indicator;LCD Display |
| Transfer time | 0ms |
| Protection | Input over-voltage, battery under voltage, overload, short circuit, over temperature |
| Communication port | Standard RS232, Dry contract for optional |
| Temperature | (0°C-40°C) in working |
| Alarm | Battery low-voltage, mains abnormal, UPS Fault |
| Humidity | 0%-95%(No condensing) |
| Noise(dB) | <60dB(within 1 meter) |
| Dimension | D×W×H-590mm×230mm×540mm |
| Weight (Kg) | 107 Kg(Approx) |
What is the DRESDEN-LF1103 Online UPS?
It is a 3kVA true online double-conversion UPS providing stable and uninterrupted power.
Who is the official importer in Bangladesh?
TNS Engineering Ltd.
What type of UPS is it?
Online double-conversion UPS.
What is the power rating?
3kVA / 2.7kW.
What is the input voltage range?
165–275V AC.
What is the output voltage regulation?
220/230V ±0.5%.
What type of batteries does it use?
12V sealed lead-acid batteries, 4 × 12V.
Can external batteries be connected?
Yes, to extend backup time.
How long is the typical backup time?
10–15 minutes at full load.
What is the battery recharge time?
Around 8 hours to reach 90%.
Does it support hot-swappable batteries?
Yes.
Can it operate without batteries?
No, batteries are required.
What is the transfer time between mains and battery?
Zero milliseconds (0ms).
What is the efficiency of the UPS?
Up to 89% in AC mode.
What protections are built-in?
Overload, short circuit, overvoltage, undervoltage, battery failure, and over-temperature.
What is the overload capacity?
125% load for 1 minute, 150% load for 200ms.
Does it protect against surges and spikes?
Yes, with AVR and surge protection.
Can it handle non-linear loads?
Yes, within rated capacity.
Where can it be used?
Data centers, servers, banks, telecom, and medical devices.
Is it compatible with generators?
Yes, diesel and petrol generators.
Can it be used for home appliances?
Yes, if within capacity.
Is it suitable for sensitive medical equipment?
Yes, pure sine wave output.
Can it run motors or ACs?
Small motors only; heavy loads not recommended.
Can it power IT equipment?
Yes, ideal for servers and networking devices.
What communication ports are available?
RS232 standard; optional SNMP and dry contacts.
Is remote monitoring supported?
Yes, via SNMP card.
Does it have an LCD display?
Yes, showing status, battery, and faults.
Can alarms be configured?
Yes, audible and visual alarms.
Can it be monitored via network?
Yes, with SNMP adapter.
What is the operating temperature range?
0°C to 40°C, humidity up to 95% non-condensing.