HANOVER-LX-120KVA

HANOVER-LX33120

Product Code HANOVER-LX33120
Status Call for price

Features

Brand: G-Mac

Status: Stock Available

Specification:

MAIN FEATURE
Capacity 120KVA/96KW
MODEL  HANOVER-LX33120
Brand G-Mac
Brand Origin Germany
Technology IGBT inverter and output isolation transformer
INPUT
Phase 3Φ+N+PE
Rated voltage 380/400/410
Frequency Range 40-70(Automatically Select Synchonization range according to grib frequency)
Bypass Range ±20%
Battery Voltage 384VDC
Battery Quantity 32PCS (29-32PCS can be adjustable)
OUTPUT
Phase 3Φ+N+PE
Voltage 380/400Vac
Voltage regulation ±1%
Frequency AC mode: tracking bypass input in synchronous State, Battery mode:50/60Hz±0.1%
Waveform <3%(Linear load); <5%(Non-lineload)
Power factor 0.8/0.9(option)
Pack Factor 3:1
Overload When the load is less than or equal to 125%, it can be to the bypass output after 10 minutes; when the load is more than 150%, it can turn to the bypass outpot after 1 minutes
OTHERS
Efficiency  AC mode:>92%, ECO mode:>98%
Transfer time 0ms
Protection Output short circuit protection, overload, over temperature, battery low-voltage, over/under voltage, fan fault, etc.
Communication port Standard RS485, Dry contract, USb, for optional:SNMP
Temperature Working (0°C-55°C), Stroage(-5°C-60°C)-(No condensing)
Humidity 0%-90%(No condensing)
IP level IP 20
Noise(dB) <65dB(within 1 meter)
Dimension  D×W×D-739mm×805mm×1405mm
Weight (Kg) 680 Kg

Description :

Applications:

  • Data Centers: Ensures uninterrupted operation for servers and networking equipment.
  • Industrial Systems: Supports CNC machines, automation lines, and production facilities.
  • Commercial Facilities: Provides reliable power for offices, banks, and retail environments.
  • Telecom Systems: Maintains stable operation for telecom base stations and networks.
  • Medical and Banking Systems: Protects sensitive equipment such as diagnostic devices, ATMs, and banking systems.
  • Precision Instruments: Guarantees clean, stable power for laboratories and measuring devices.
  • Other Critical Infrastructure: Ideal for any facility where uninterrupted, high-quality power is essential.

Main Features:

  • IGBT Inverter with Output Isolation Transformer: High efficiency and stable output.
  • Online Double Conversion Technology: Provides continuous, clean sine wave power.
  • Wide Input Voltage Range: Compatible with fluctuating and unstable power conditions.
  • Communication Ports: RS232/RS485 for remote monitoring.
  • Optional SNMP Adapter/Dry Contact: Network-based monitoring and management capability.
  • High Reliability and Performance: Designed for mission-critical applications.
  • External Battery Pack (Optional): Expandable backup time for extended power support.
  • Maintenance Switch: Allows safe service and maintenance without shutting down the load.
  • Advanced Protection Features: Includes overload, short-circuit, surge, and low-battery protection.
  • User-Friendly LCD Display: Shows input/output voltage, battery status, load, and alarms for easy monitoring.

Question :

1. What is the capacity of the HANOVER 120KVA UPS?
It has a rated capacity of 120KVA / 108KW, ideal for large-scale industrial and IT applications.

2. Is the HANOVER 120KVA a double-conversion online UPS?
Yes, it is a true online UPS ensuring uninterrupted, stable, and clean power supply.

3. What input voltage does it support?
It supports a wide three-phase input of 380/400/415V AC.

4. What is the output voltage of the UPS?
It provides a regulated three-phase 380/400/415V AC pure sine wave output.

5. What is the output power factor?
The UPS delivers a high power factor of 0.9, making it highly efficient.

6. What frequency does it maintain?
It maintains a stable output frequency of 50Hz or 60Hz.

7. What type of batteries does it use?
It uses SMF (Sealed Maintenance-Free) or VRLA lead-acid batteries.

8. What is the required battery bank voltage?
Typically 384V DC (32 pieces of 12V batteries connected in series).

9. How much backup time can it provide?
Standard runtime is 10–15 minutes, extendable with external battery cabinets.

10. Can external batteries be added?
Yes, additional battery banks can be connected to increase backup time.

11. Does the HANOVER 120KVA UPS support remote monitoring?
Yes, it supports RS232, USB, and optional SNMP for LAN/WAN monitoring.

12. Does it come with an LCD panel?
Yes, it includes an intelligent LCD/LED display showing status, alarms, and system information.

13. Is it compatible with generators?
Yes, it works efficiently with diesel or gas generators.

14. What is the UPS efficiency?
It provides up to 95% efficiency in online double-conversion mode.

15. Can it be used in data centers?
Yes, it is widely used for large-scale data centers and IT infrastructure.

16. Is it suitable for industrial machinery?
Yes, it supports CNC machines, automation systems, and heavy-duty equipment.

17. Can hospitals use this UPS?
Yes, it provides clean, stable power for hospitals, labs, and diagnostic devices.

18. What protections does it offer?
It includes overload, short-circuit, over-voltage, surge, and low-battery protection.

19. Does it have bypass options?
Yes, both manual and automatic bypass are included.

20. Does it feature auto-restart function?
Yes, it restarts automatically when utility power returns.

21. What is the battery lifespan?
Batteries typically last 3–5 years, depending on operating conditions.

22. How often should batteries be replaced?
Normally every 3 years, depending on usage and environment.

23. What is the noise level of this UPS?
It operates at less than 62dB under normal load conditions.

24. Does it need professional installation?
Yes, due to high capacity, professional installation is required.

25. Can its backup be expanded later?
Yes, you can add external battery banks for longer backup.

26. Does it include smart charging technology?
Yes, it uses intelligent battery management for extended battery life.

27. How easy is it to maintain?
It requires minimal maintenance, mostly battery and ventilation checks.

28. What is the approximate weight of the HANOVER 120KVA UPS?
It usually weighs between 900–1200 kg depending on configuration.

29. Where is this UPS commonly used?
It is used in telecom, banks, large industries, hospitals, government, and IT infrastructure.

30. Why choose HANOVER 120KVA UPS?
Because it ensures maximum reliability, high efficiency, advanced monitoring, and strong protection for mission-critical operations.